Installation Height Of Encapsulated Dry Type Transformer
The installation of encapsulated dry type transformer requires a certain height, and various installations must be strictly implemented according to the relevant installation regulations of power equipment, so as to ensure the continuous improvement of the performance and efficiency of dry-type transformers. The height requirements for dry-type transformers during installation are as follows:
(1) The distance between the outline of a encapsulated dry type transformer of 10kV and below and the surrounding fence or wall should consider the convenience of dry-type transformer transportation and maintenance, and the distance should not be less than 1m; in the direction of operation, a distance of more than 2m should be left ;If a metal fence is used, the metal fence should be grounded, and warning signs should be hung in obvious places;
(2) The height of the dry-type transformer transformer pier installed on the ground is generally 0.5m, and a fence of not less than 1.7m should be installed around it, and warning signs should be hung in obvious places;
(3) The encapsulated dry type transformer of 315kVA and below can be installed on the pole. The distance between the bottom and the ground should not be less than 2.5m; the distance between the live part and the ground should not be less than 3.5m;
(4) The transformer platform on the column should be stable and firm, and the waist rail should be wound with Φ4.0mm galvanized iron wire for more than 4 turns and an even number. The iron wire should not have joints, and it should be tightened after winding. m;
(5) The installation position of the secondary insurance on the column and the ground changing platform shall meet the following requirements:
1) If there is an isolating switch on the secondary side, it should be installed between the isolating switch and the low-voltage insulator, or a fuse is used as the isolating switch;
2) If there is no isolating switch on the secondary side, it should be installed on the outside of the low-voltage insulator, and the insulated wire should be bridged across the insulated wires at both ends of the fuse;
(6) All high and low voltage leads on the pole and on the ground transformer should use insulated wires;
The above are the common requirements for the installation height of encapsulated dry type transformer for your reference. For the installation height of dry-type transformers, the quality of installation should be continuously improved, and the installation height of dry-type transformers and installation engineering should be continuously carried out. The main regulations, for more information about dry-type transformers, please communicate and communicate with our manufacturers.